Auglaize Soil and Water Conservation District 

Home Up Events News Related Sites Search Services

 

 

 

 

Controlling Algae
Dry Hydrants
Fish Kills
Pond Management

DRY HYDRANTS

 

 

 

Dry Hydrants give Added Fire Protection

A dry hydrant is a non-pressurized, low cost pipe system installed along the bank of a pond or other body of water. The top of the pipe extends vertically above the ground in a place for easy access and is fitted with an elbow and cap for hook-up. The other end of the pipe extends out into the pond to a depth of 4 to 8 feet. The materials needed for a dry hydrant include: 6 inch (or larger) PVC Schedule 40 pipe, hose connection compatible with local fire department equipment, two elbows and a strainer with cap. The amount of PVC pipe needed depends on the location of the hydrant. The most limiting factor is the vertical length.

Water cannot be lifted by suction greater than 20 feet. The hose connection must be two feet above ground so the depth below ground to the water in the pipe cannot be greater than 18 feet. A preferred depth is somewhere between 5 and 10 feet.

A 1500 gallon pumper truck would have to fill up four times to lower the water 1 inch in a 1/4 acre pond!

 

More on Dry Hydrants:

 

 

 

 

Home ] Controlling Algae ] [ Dry Hydrants ] Fish Kills ] Pond Management ]